Sizing a circulator pump for a small heating loop
A circulator is chosen by two numbers: flow, the water the loop must move, and head, the resistance the pump has to overcome to move it.
Flow
Flow follows the heat the loop has to deliver. A handy rule: gallons per minute = BTU per hour ÷ (500 × the temperature drop in °F). A 40,000 BTU/h loop designed for a 20 °F drop needs about 4 GPM.
Head
Head is the friction of the longest loop at that flow: pipe, fittings, valves and the boiler. Small residential loops often land between 5 and 15 feet.
Reading the curve
Mark your flow and head on the pump curve and pick the model whose curve passes at or just above that point. A variable-speed circulator adjusts itself as zones open and close.
Bring to the counter
- Heat load and design temperature drop.
- Pipe size and length of the longest loop.
- Zone valves and other fittings on it.
- The model of the old pump, if there is one.