Sizing a circulator pump for a small heating loop

A circulator is chosen by two numbers: flow, the water the loop must move, and head, the resistance the pump has to overcome to move it.

Flow

Flow follows the heat the loop has to deliver. A handy rule: gallons per minute = BTU per hour ÷ (500 × the temperature drop in °F). A 40,000 BTU/h loop designed for a 20 °F drop needs about 4 GPM.

Head

Head is the friction of the longest loop at that flow: pipe, fittings, valves and the boiler. Small residential loops often land between 5 and 15 feet.

Reading the curve

Mark your flow and head on the pump curve and pick the model whose curve passes at or just above that point. A variable-speed circulator adjusts itself as zones open and close.

Bring to the counter

  • Heat load and design temperature drop.
  • Pipe size and length of the longest loop.
  • Zone valves and other fittings on it.
  • The model of the old pump, if there is one.